EATON CORPORATION TRIPP LITE 5.8kW Single-Phase 208/240V ATS/Monitored PDU L6-30R Outlet 2 L6-30P Inputs 1U Rack-Mount

Redcorp# 57904456 Article# PDUMNH30HVAT
€ 1012,31 Hors TVA
A partir de € 988,66 Détails
Quantité
-
1
+
TRIPP EATON CORPORATION TRIPP LITE 5.8kW Single-Phase 208/240V ATS/Monitored PDU L6-30R Outlet 2 L6-30P Inputs 1U Rack-Mount
Pour une aide personnalisée ou une livraison plus rapide

+32 2 558 30 00

The PDUMNH30HVAT 5.8kW Single-Phase 208/240V ATS/Monitored PDU provides remote power monitoring and enables redundant power for network devices with non-redundant power supply configurations. Ideal for data centers and server rooms, it mounts in 1U of space in EIA-standard 19-inch racks and features one L6-30R outlet—perfect for connecting a single device or a 0U 208/240V PDU with an L6-30P plug. Dual 3.05 m (10-ft.) input cords with L6-30P plugs connect to separate primary and secondary single-phase power sources. The PDU constantly evaluates the power quality of both input sources. Dynamic solid-state (TRIAC) automatic transfer switching allows the PDU to switch to the secondary source within 1–5 milliseconds should the primary source fail or become unstable to ensure your connected equipment operates without interruption. Built-in Ethernet network interface allows remote access to the PDU for power monitoring, configuration, control and notifications via web browser, SSH, telnet or SNMP. Provides real-time load/current data with billing-grade accuracy (+/- 1 percent). Tiered access privileges allow both an administrator and a guest to log in. Automated alerts help prevent accidental overloads, power loss and downtime. Digital display indicates power availability, voltage, source A/B input status, output load and power factor, as well as temperature and humidity conditions with the optional ENVIROSENSE module (sold separately).

- Two single-phase L6-30P inputs with 3.05 m (10-ft.) cords
- L6-30R outlet for connecting single device or 0U vertical PDU
- Automatic transfer switching within 1–5 ms
- Ethernet network interface for remote access
- Digital LED display for real-time status monitoring

- Provides remote power monitoring and enables redundant power for network devices with non-redundant power supply configurations
- Dual 3.05 m (10-ft.) input cords with L6-30P plugs connect to separate primary and secondary single-phase power sources
- Connects a single device or indirectly powers equipment through a 0U 208/240V PDU with L6-30P input (sold separately)
- Dynamic solid-state (TRIAC) automatic transfer switching
- Switches to secondary power source if primary source fails or becomes unstable
- 1–5 ms transfer time ensures uninterrupted operation of connected equipment
- Built-in processor monitors both sources and prevents switching if secondary source is unavailable or of lower quality than primary source
- Reports source A and source B input power status and other information, including power availability, line voltage, frequency, amps, kilowatts and power factor
- Built-in Ethernet network interface allows full remote access for power monitoring, configuration, control and notifications via web browser, SSH, telnet or SNMP
- Real-time load/current data with billing-grade accuracy (+/- 1 percent)
- Tiered access privileges allow both an administrator and a guest to log in
- Automated alerts help prevent accidental overloads, power loss and downtime
- Optional ENVIROSENSE module (sold separately) monitors temperature and humidity
- 10/100 Mbps auto-sensing allows optimal communication with 10/100 Base-T networks
- Supports HTTP, HTTPS, PowerAlert®, SMTP, SNMPv1, SNMPv2, SNMPv3, Telnet, SSH, FTP, DHCP, BOOTP and NTP
- Compatible with EIA-standard 19 in. 4-post racks and rack enclosures
- Optional PDU4PKIT rail kit adds rear rack-mounting support

Specs
Design
Avec contrôle en ligne
1U
horizontale
Métal
Noir
LCD
Connectivité
1 sortie(s) CA
NEMA L6-30P
NEMA L6-30P
1
Caractéristiques
3 m
Tested to UL/CSA 60950-1 (USA, Canada), FCC Class A (Emissions), NOM (Mexico)
Puissance
200-240 V
50 - 60 Hz
30 A
200-240 V
5800 W
Poids et dimensions
430 mm
355,6 mm
430 x 356 x 44 mm
43,7 mm
6,97 kg
Informations sur l'emballage
550 x 525 x 190 mm
8,41 kg
549,9 mm
525 mm
190 mm
Conditions environnementales
0 - 50 °C
-15 - 60 °C
5 - 95%
0 - 3000 m
32 - 122 °F
Détails techniques
RoHS
Données logistiques
Chine
1 pièce(s)


Results