Technology adapted to sensitive needs

The E4 LCD ProTM range features microprocessor-controlled On Line Double Conversion technology, which delivers pure sine wave output current for mission critical applications. In order to protect the most sensitive equipment and to adapt to industrial uses requiring high power, these devices are equipped with the latest generation of IGBTs on their rectifier and UPS circuits.

Smart features

Cold start function: in case of emergency, compensates for a total power cut by starting the UPS via battery-use. - Microprocessor-based UPS control: offers a wide voltage range input, high input power factor, low harmonic distortion and marked noise level reduction. - EPO (emergency power off) function: ensures safety of personnel and equipment in the event of fire or any other emergency by triggering a total and immediate shutdown of the UPS. - Manual bypass: Included as standard with the static Bypass, it allows continuous power to connected equipment during UPS maintenance work via a rotary switch and thus avoids shutdown of the computer network.

Designed for ease of use

An intuitive LCD display allows immediate viewing of the UPS status. The control panel allows direct control from the front panel: on/off, configuration of the operating mode, etc.

Communication

USB and RS232 communication ports and the SNMP interface allow E4 LCD Pro TM UPSs to communicate with the various workstations and computer servers they protect. The UPS has multiple communication possibilities: USB or RS232 ports can thus operate simultaneously with the SNMP interface (optional).

Extended backup time version

Available in Long Autonomy version (S version), without internal batteries but with additional battery cabinets.

Specs
Features
Double-conversion (Online)
10 kVA
8000 W
Pure sine
190 V
520 V
46/64 Hz
208 V
240 V
46/64 Hz
-1 - 1%
3
1
91%
0.8
0.8
3:1
6%
60 dB
Alarm when on battery, Fault, Overload alarm, Low battery alarm
Ports & interfaces
Terminal
1
USB Type-B
RS-232
Battery
Sealed Lead Acid (VRLA)
9 Ah
12 V
12 min
9 h
4 A
Design
Tower
Black
LCD
CE
Operational conditions
0 - 40 °C
0 - 95%
0 - 1000 m
Technical details
RoHS
Weight & dimensions
190 mm
442 mm
668 mm
76 kg
84 kg
Packaging data
RS-232, USB cable